Home > Products Introduction > Temp.controller   
   
 Summary
Programmable
PID
General
Special Purpose
Indicator
Others
 

?
 
     * TH300
    - TFT LCD screen with touch panel function
  - 300 patterns(6000 segments in total)
  - 4 Contact inputs(D.I), 12 Digital outputs
  - Communication function(RS232, RS485/422)

 
             
 
     
 

Input
Input Dry and wet bulb sensor : RTD (Pt100 目 IEC751)
Temperature sensor : RTD (Pt100 目 IEC751)
Humidity sensor : (4 - 20) mA current output(input resistance : approx 1M目)
Sampling cycle : 500 ms
Measurement range Temperature(﹉C) : -100.0 ~ 500.0
Humidity(%RH) : 0.0 ~ 100.0
Indication accuracy Temperature : ▽0.2 % of F.S
Humidity : ▽2% of F.S
Contact input (D.I) 4 contacts (1a x 4)

Output
Control output S.S.R ON : 24 V d.c pulse voltage, OFF : Max. 0.1 V d.c / Pulse voltage (load resistance min 800 目)
Cycle time : 1 ~ 1000 sec
Trs • output Temperature side 4 - 20 mA d.c(load resistance min Max. 600 目) PV, MV, SV *by the internal selection
Humidity side
Resolving power Max. 8000 (regarding the 4 - 20 mA)
Renewal power 500 ms
Digital output Contact 8 contacts (1a x 8 contacts) / N.O : 30 V d.c 5 A, 240 V a.c 5 A
Transistor 4 contacts (open collector output) 24 V d.c 300 mA max

Power
Power supply voltage (100 - 240) V a.c, voltage fluctuation : ▽10%
Power frequency (50 - 60) Hz
Power consumption 10 VA max
Insulation resistance Between the 1st and 2nd terminal 500 V d.c 10 M目 min
Between the 1st / 2nd terminal and earth terminal
Dielectric strength Between the 1st and 2nd terminal 2500 V a.c, 50/60 Hz

Model Code Description
TH300 Progammable Temperature • Humidity Controller / 96(W) x 96(H) x 100(D)
Communication 1   RS232C
2   RS485/422
Language 1 Korean / English (standard type)
2 English /Chinese (simple type)
3 English /Chinese (traditional type)