| MODEL |
UX100 |
|
Appearance (mm) |
48(W)Ӿ24(H)Ӿ100(D) |
|
Function |
| ¤żFuzzy |
¤żUniversal-input |
| ¤żHeating / Cooling control |
¤żIP 65 front facia |
| ¤żHeating / Cooling hysteresis |
¤żInput correction |
| ¤ż”ĘC / ¢µ selectable |
¤żOutput Limitation |
| ¤żARW |
¤żAlarm output |
| ¤żInterface (RS485) |
¤żAuto tuning |
| ¤żInput filter : OFF, 1~120sec. |
|
|
| Input |
Thermocouple
: K, J, E, T, R, S, B, L, N, U, WRe 5-26, PL-II
R.T.D : Pt 100§Ł, KPt 100§Ł
Direct voltage : 1~5V, 1~10V, -10~20mV, 0~100mV
--------------(Free scale type) |
|
Sampling cycle |
250ms |
|
Input display resolution |
Below decimal point of Input signal and Measuring range |
| Input
impedance |
T / C
and mV input : Min, 1M„Ų DC V : 1M„Ų |
|
Source tolerable resistance |
Thermocouple
: Max. 250§Ł, Voltage : Max. 2k„Ų |
|
Lead wire tolerable resistance |
R.T.D
: Max. 150§Ł / wire |
|
Input tolerable voltage |
”¾10V
(T / C, R.T.D, Voltage : mV DC), ”¾20V(Voltage : V DC) |
|
Noise removal rate |
NMRR(Nomal
mode) : 40dB min.
CMRR(Common mode) : 120dB min.(50 / 60Hz ”¾1%) |
| Standard |
T / C,
R.T.D : KS, IEC, DIN |
| Scaling |
According
to setting Max. value(SH), Min.
value(SL) of measuring range,
scaling is available (-1999~9999) |
|
Standard junction temp. |
”¾1.5”ĘC(15~35”ĘC),
”¾2.0”ĘC(0~50”ĘC) |
|
Burn-oup |
T / C
: Up / Down scale selectable
R.T.D : UP scale selectable (Detection current : 50nA) |
| Accuracy |
”¾0.5%
(Full scale) |