Home > Products Introduction > Temp.controller   
   
 Summary
Programmable
PID
General
Special Purpose
Indicator
Others
 

?
 
     * UX100
    - P.I.D auto tuning
  - Scaling/input correction
  - Heating/Cooling control
  - Communication (RS485)

 
             
   
     
 

MODEL UX100
Appearance (mm) 48(W)Ӿ24(H)Ӿ100(D)
Function
¤żFuzzy ¤żUniversal-input
¤żHeating / Cooling control ¤żIP 65 front facia
¤żHeating / Cooling hysteresis ¤żInput correction
¤ż”ĘC / ¢µ selectable ¤żOutput Limitation
¤żARW ¤żAlarm output
¤żInterface (RS485) ¤żAuto tuning
¤żInput filter : OFF, 1~120sec.
Input Thermocouple : K, J, E, T, R, S, B, L, N, U, WRe 5-26, PL-II
R.T.D : Pt 100§Ł, KPt 100§Ł
Direct voltage : 1~5V, 1~10V, -10~20mV, 0~100mV
--------------(Free scale type)
Sampling cycle 250ms
Input display resolution Below decimal point of Input signal and Measuring range
Input impedance T / C and mV input : Min, 1M„Ų DC V : 1M„Ų
Source tolerable resistance Thermocouple : Max. 250§Ł, Voltage : Max. 2k„Ų
Lead wire tolerable resistance R.T.D : Max. 150§Ł / wire
Input tolerable voltage ”¾10V (T / C, R.T.D, Voltage : mV DC), ”¾20V(Voltage : V DC)
Noise removal rate NMRR(Nomal mode) : 40dB min. CMRR(Common mode) : 120dB min.(50 / 60Hz ”¾1%)
Standard T / C, R.T.D : KS, IEC, DIN
Scaling According to setting Max. value(SH), Min. value(SL) of measuring range,
scaling is available (-1999~9999)
Standard junction temp. ”¾1.5”ĘC(15~35”ĘC), ”¾2.0”ĘC(0~50”ĘC)
Burn-oup T / C : Up / Down scale selectable R.T.D : UP scale selectable (Detection current : 50nA)
Accuracy ”¾0.5% (Full scale)

Model Code Description
UX100 - Process temperature controller. 48(W) x 24(H) x 100(D) mm
Control type 0 Universal
1 Heating / Cooling (Unable to use relay at heating)
Option 0 None
1 Communication function(RS485)