| Model |
KF9 |
KF7 |
KF2 |
KF4 |
| Appearance |
 |
| 96(W) x 96(H)
x 100(D) |
|
 |
| 72(W) x 72(H) x
100(D) |
|
 |
| 48(W) x 96(H) x
100(D) |
|
 |
| 48(W) x 48(H) x
100(D) |
|
| Power Voltage |
100 - 240V AC, 50 - 60 Hz(voltage fluctuation rate: ▽10%) |
| Power Consumption |
Approx. 3 VA |
|
Input |
Thermocouple, RTD, voltage/current |
| Control Output |
Relay:250 V a.c 3A(resistive load), SSR:12V d.c Voltage Pulse(load resistor: above 800目),
Current: 4~20 mA d.c(load resistor: below 600目) |
| Control Method |
Proportional Control of ON / OFF |
| Alarm Output |
Relay:250V AC 3A
≦Except, KF4 model |
| Setting Method |
Setting by the digital switch |
| External Input Resistor |
Thermocouple: below 100目, Resistive: below 10目 / each wire |
| Indicated Range |
Setting temperature range |
| Indicated Method |
Digital indicator |
Setting or
Indicator accuracy |
Below ▽0.5% of F.S, Below ▽1.0% of setting range |
| Adjusting Sensitivity |
Approx. 0.2% F.S(fixed) |
| Proportional Cycle |
Relay: 25 ~ 30 sec, SSR: 2 ~ 4 sec |
| Reset Range |
above ▽1.5% of max. range(variableness) |
| Dielectric Strength |
2000 V a.c, 50 / 60 Hz, for 1 min. (between the terminals of the two-polar current carry part) |
Vibration
Resistance |
Malfunction |
2 ~ 55 Hz each X ﹞ Y ﹞ Z direction for 10 minutes |
| Durability |
10 ~ 55 Hz, 0.76 mm, each X ﹞ Y ﹞ Z direction for 2 hours |
Shock
Resistance |
Malfunction |
100 m/s2 3 times at each 6 direction(approx. 10G) |
| Durability |
300 m/s2 3 times at each 6 direction(approx. 10G) |
Life
Expectancy |
Malfunction |
Above 10 million times(relay type) |
| Durability |
Above 300 thousand times(relay type) |
Operating Ambient
Temperature/Humidity |
0 ~ 50 ﹎, 35 ~ 85% RH(with condensation) |
| Model |
Suffix code |
Description |
| KF |
- |
 |
 |
 |
 |
 |
 |
Digital Temperature controller |
| Appearance |
2 |
|
|
|
|
|
|
48(W) x 96(H) x 100(D) mm |
| 4 |
|
|
|
|
|
|
96(W) x 48(H) x 100(D) mm |
| 7 |
|
|
|
|
|
|
72(W) x 72(H) x 100(D) mm |
| 9 |
|
|
|
|
|
|
96(W) x 96(H) x 100(D) mm |
| Control type |
F |
|
|
|
|
|
ON / OFFcontrol(select with dip switch in) |
| P |
|
|
|
|
|
proportion control |
| O |
|
|
|
|
|
Indicator(only indication) |
| Input |
K |
|
|
|
|
K Thermocouple |
| J |
|
|
|
|
J Thermocouple |
| R |
|
|
|
|
R Thermocouple |
| D |
|
|
|
|
R.T.D KPt 100 目 |
| P |
|
|
|
|
R.T.D Pt 100 目 (IEC) |
| V |
|
|
|
|
1 - 5 V d.c |
| C |
|
|
|
|
4 - 20 mA d.c |
| Control output |
M |
|
|
|
Relay |
| C |
|
|
|
S.C.R(current output, 4 - 20 mA d.c) |
| S |
|
|
|
S.S.R(voltage pulse output, 12 V d.c) |
| Alarm output (except KF4) |
N |
|
|
None |
| O |
|
|
upper limit alarm |
| P |
|
|
lower limit alarm |
| W |
|
|
upper ? lower limit alarm |
| Control action(self select) KF4 just in demand |
R |
|
reverse action(heat control) |
| D |
|
RET(transmission output, 4 - 20 mA d.c measured value ) |
| Range code |
|
| Code NO. |
INPUT |
Temp. Range |
| 2 |
Pt |
-99 ~ 99 |
| 4 |
4 ~ 20 mA |
0 ~ 99 |
| 1 ~ 5 V |
| 8 |
Pt, K, J |
0 ~ 399 |
| 11 |
K |
0 ~ 999 |
| 12* |
0 ~ 1199 |
| 13* |
PR(R) |
600 ~ 1699 |
| * Code No, 12 & 13 are not available for KF2, KF4 |
|