 Summary
Programmable
PID
General
Special Purpose
Indicator
Others
 

?
 
     * HY series - analog
    - Simple temperature set up
  - Proportioning control or ON/OFF control
  - Burn out (Output OFF when sensor disconnected)
  - Plug in type, (simple correcting, checking and exchanging)

 
             
     
 

Model HY-1000 HY-2000 HY-3000
Appearance
Input Thermocouple(K,J), R.T.D (DIN/JIS Pt 100戒)
accuracy 1% of full scale or ▽2﹉C [3﹉F] (Whichever is larger)
Power supply a.c 110V/220V (50/60忍)
Control action
Time proportioning
(With manual reset)
Continuous proportioning
(With manual reset)
ON/OFF Control : Hysteresis
Time proportioning (Proportional band: 3% of full scale)
ON/OFF Control : Hysteresis
Control output
Relay contact : a.c 250V 3A
(Resistive load) 1C (NO,NC) contact
SSR driving : 0/12V d.c
(Constant voltage pulse)
[load resistance more than 800戒]
Current : 4~20mA d.c
[load resistance less than 600戒]
Relay contact : a.c 250V 3A (Resistive load) 1C (NO,NC) contact
Alarm output None
Ambient temperature 0 ~ 50﹉C(32~122﹉F) ≦Ambient humidity : 35 ~ 85% RH
Net weight Approx. 260g Approx. 440g

Model HY-4500S HY-4700S HY-5000
Appearance
Rated Voltage 110 V a.c / 220 V a.c, 60 Hz
Permissible Voltage
Fluctuation Range
Rated Voltage ▽ 10%
Consumption Power Approx. Max 3 VA
Input Thermocouple, Resistive, d.c Current, d.c Voltage(see Standard Range Code)(Built - in Burnout circuit)
Adjusting Sensitivity ▽0.2%(fixed) of Max. Range
Control Method Proportional Control, ON / OFF Control
Setting Method Analog Setting
Display Method Analog Display
Control Output
Relay output : Capacity 250 V a.c 3 A (Resistive Load) contact : 1c
SSR Output : 12 V a.c (Constant Voltage Pulse) (Resistive Load : above 800 目)
Current Output : 4 - 20 mA d.c (Resistive Load : below 600 目)
Setting accuracy 2 % of Max. Range
Display accuracy Below ▽2.0 % of Max. Range
Alarm Operation High Limit Operation, Low Limit Operation, High / Low Limit Operation
Proportional Band 1 ~ 10 % of Max. Range(variable) 1 ~ 3 % of Max. Range(variable) 3 % of Max. Range(fixed)
Proportional Cycle Relay Output : 20 ~ 30 sec / SSR Output : 2 ~ 4 sec
Insulation Resistance Above 100 M目 (500 V a.c mega)
Dielectric Strength 2000 V a.c 50 ~ 60 Hz for 1 minute
Noise Immunity Squared wave noise(pulse width : 1000 伊s) ▽1 KV
Vibration Resistance 10 - 50 Hz (cycle for 1 minute), double amplitude : 0.75 mm, each X Y Z direction for 1 hour
Shock 300 m/s昌 (approx. 30G)
Relay Life Expectancy Mechanical : above 10 millions times
Electrical : above 100 thousands times (250 V a.c, 3 A Resistive Load)
Operating Ambient
Temperature / Humidity
0 ~ 50 ﹉C, 35 ~ 85 % R.H. (without condensation)
Weight * 658 g * 358 g
* including brackets

Model Suffix Code Description
HY- / AF1- Standard Model HY-1000 / 2000 / 3000 / AF1
Adjusting action F 2-Position Control(ON / OFF)
P Proportional action
Input K K (CA)
J J (IC)
R R (PR 13%)
D Pt100 目 (KS Standards)
P Pt100 目 (DIN Standards)
V *1 - 5 V d.c
C *4 - 20 mA d.c
Control Output M Relay contact
C *Current (4 - 20 mA d.c)
S *SSR driving (Voltage Pulse 12 V d.c)
Alarm Output or Operation N None
O High Limit Operation Alarm Output
P Low Limit Operation Alarm Output
W High / Low Limit Operation Alarm Output
Control action R Reverse action Control (for Heating Control)
D Direct action Control (for Cooling Control)
Range code Standard Range Code Number Selection
* Non-display product does not have the feature


Model Suffix Code Description
HY- Standard Model HY-4500S / 4700S / 5000
Adjusting action F 2-Position Control(ON / OFF)
P Proportional action
Input K K (CA)
J J (IC)
R R (PR 13%)
D Pt100 目 (KS Standards)
P Pt100 目 (DIN Standards)
V 1 - 5 V d.c
C 4 - 20 mA d.c
Control Output M Relay Output
C Current (4 - 20 mA d.c)
S SSR driving (Voltage Pulse 12 V d.c)
Alarm Output or Operation N None
O High Limit Operation Alarm Output
P Low Limit Operation Alarm Output
W High / Low Limit Operation Alarm Output
Control action R Reverse action Control (for Heating Control)
D Direct action Control (for Cooling Control)
Range code Standard Range Code Number Selection

Model /
Code No.
HY-1000 HY-2000 / 3000 AF1
Input Temp. Range Input Temp. Range Input Temp. Range
1 Pt -50 ~ 50     Pt -99 ~ 99
2     Pt -50 ~ 100    
3 Pt 0 ~ 100     Pt 0 ~ 99
4     Pt, K, J 0 ~ 100 Pt, K 0 ~ 199
5 Pt, K 0 ~ 200 Pt, K, J 0 ~ 200 Pt, K 0 ~ 299
6 Pt, K 0 ~ 300 Pt, K, J 0 ~ 300 Pt, K 0 ~ 399
7 Pt, K 0 ~ 400 Pt, K, J 0 ~ 400    
8 K 0 ~ 600 K 0 ~ 600    
9 K 0 ~ 800 K 0 ~ 800    
10 K 0 ~ 1200        
11     K 0 ~ 1200    
12     R 0 ~ 1600    

Model /
Code No.
HY-4500S HY-4700S HY-5000
Input Temp. Range Input Temp. Range Input Temp. Range
1 Pt -50 ~ 50 Pt -50 ~ 50 Pt -50 ~ 50
2            
3 Pt -50 ~ 100 Pt -50 ~ 100 Pt 0 ~ 100
4            
5 Pt 0 ~ 100 Pt 0 ~ 100 Pt, K 0 ~ 200
6         Pt, K 0 ~ 300
7 Pt, K 0 ~ 200 Pt, K 0 ~ 400 Pt, K 0 ~ 400
8 Pt, K 0 ~ 300 Pt, K 0 ~ 600 K 0 ~ 600
9 Pt, K, J 0 ~ 400 Pt, K, J 0 ~ 800 K 0 ~ 800
10 K 0 ~ 600 K   K 0 ~ 1200
11 K 0 ~ 800 K 0 ~ 1200    
12       0 ~ 1600    
13 K 0 ~ 1200 K      
14 R 0 ~ 1600 R