Home > Products Introduction > Temp.controller   
   
 Summary
Programmable
PID
General
Special Purpose
Indicator
Others
 

?
 
     * AF1
    - Simple temperature set up due to BCD S/W
  - Display temperature using variation of measured value

 
             
     
 

MODEL AF1
Appearance (mm) 48(W)x96(H)x100(D)
Power voltage AC 110/220V ( 50/60Hz )
Power consumption 3VA
Input T/C, R.T.D
Control output
Relay contact : AC 250V 5A ( Resistive load ),
SSR : DC12V ( Constant voltage pulse )( Load resistance more than 800§Ù )
Control action Proportional or ON/OFF control
Alarm output Relay contact : AC 250V 5A
Alarm setting Variation setting for SV
Setting by B.C.D switch
External input resistance Thermocouple : Max. 100§Ù/wire
Display Temp. Range Setting value
Display Analog
Setting and display accurary Setting temperature : within ¡¾2% of Max. Temp. Range,
Display accuracy : Whthin ¡¾2.5% of Max. Temp. Range
Control sensitivity Max. 0.2%, F¤ýS ( Fixed )
Proportional cycle Relay contact : 25 ~ 30sec SSR : 2 ~ 4sec
Reset Temp. Range ¡¾1.5% or Max. Temp. Range ( Between + and - charging terminals )
Dielectric strength AC 2,000V 50/60Hz for 1minute
2 ~ 55Hz, X, Y, Z each positions for 10 minutes
Vibration Malfuntion
Durability 10 ~ 55Hz 0.76§®, X, Y, Z each positions for 2 hours
Shock Malfuntion 100 m/s©÷ 6 positions each 3 times
Durability 300 m/s©÷ 6 positions each 3 times
Life Mechanical Max. 10millions times ( Relay type )
Electrical Max. 0.3millions times ( Relay type )
Ambient temperature and humidity 0 ~ 5¡ÆC ( 32 ~ 122¡ÆF )¤ý35 ~ 85%RH

Model Suffix Code Description
AF1 48(W) x 96(H) x 100(D) mm
Control Type F 2-Position Control(ON / OFF)
P Proportional Action
Input K K (CA)
J J (IC)
R R (PR 13%)
D Pt 100 ¥Ø (KS Standards)
P Pt 100 ¥Ø (DIN Standards)
V *1 - 5 V d.c
C *4 - 20 mA d.c
Control Output M Relay Contact
C *Current (4 - 20 mA d.c)
S *S.S.R driving (Voltage Pulse 12 V d.c)
Alarm Output N None
O High Limit Alarm Output
P Low Limit Alarm Output
W High / Low Limit Alarm Output
Control Direction R Reverse Action Control(for Heating Control)
D Direct Action Control(for Cooling Control)
Temp. Range Code Standard Temp. Range Code Number Selection
*Non-display product does not have the feature

Model /
Code No.
HY-1000 HY-2000 / 3000 AF1
Input Temp. Range Input Temp. Range Input Temp. Range
1 Pt -50 ~ 50     Pt -99 ~ 99
2     Pt -50 ~ 100    
3 Pt 0 ~ 100     Pt 0 ~ 99
4     Pt, K, J 0 ~ 100 Pt, K 0 ~ 199
5 Pt, K 0 ~ 200 Pt, K, J 0 ~ 200 Pt, K 0 ~ 299
6 Pt, K 0 ~ 300 Pt, K, J 0 ~ 300 Pt, K 0 ~ 399
7 Pt, K 0 ~ 400 Pt, K, J 0 ~ 400    
8 K 0 ~ 600 K 0 ~ 600    
9 K 0 ~ 800 K 0 ~ 800    
10 K 0 ~ 1200        
11     K 0 ~ 1200    
12     R 0 ~ 1600