| Model |
BX8 |
| Function |
| ﹞Fuzzy function |
﹞Alarm Output Function(AL-1,2) |
| ﹞Protection Structure(IP65 only the front) |
﹞Auto operation function(ST, Low PV) |
| ﹞Communication Function(RS485/422) |
﹞Heating/cooling hysteresys |
| ﹞Heater Break Alarm function(HBA) |
variation
function |
| ﹞Input multi function |
﹞Transmit Output Function(PV, SV, MV) |
| ﹞Group PID function |
﹞Input filter : OFF, 1 ~ 120 sec. |
| ﹞Zone PID function |
﹞Heating/cooling control function |
| ﹞External contact function(DI 1, DI 2) |
﹞Output Limit Function |
|
| Input Type |
| ﹞Thermocouple : K, J, E, T, R, S, B, L, N, U, WRe5 - 26, PL-II |
| ﹞RTD : Pt 100 目, KPt 100 目 |
| ﹞d.c voltage input : 1~5 V d.c(For 4~20 mA d.c input, connect 250 目(0.1%) at the |
| exterior), -10~20 mV, 0~100 mV(programmable scale method) |
|
| Sampling Cycle |
250 ms |
| Input
Display
Resolution |
Basically, below the decimal point of the input signal and measuring range |
| Input Impedance |
Thermocouple or mV input : above 1 M目, d.c V input : approx. 1 M目 |
Permissible
resistance
of signal source |
Thermocouple : below 250 目, Voltage : below 2 k目 |
Permissible
wiring resistance |
RTD : below 150 目 / single wire(but, the resistance of the 3 wires should be the same |
Permissible
input
resistance |
Within ▽10V(Thermocouple, RTD, Voltage : mV d.c), Within ▽20V(Voltage : V d.c) |
| Noise
rejection
ratio |
| NMRR(normal mode) : above 40 dB, CMRR(common mode) : above 120 dB (50/60 Hz ▽1%) |
|
| Applied standard |
Thermocouple / RTD(KS / IEC / DIN) |
Compensation
error
at standard contact |
▽1.5 ﹉C(15 ~ 35 ﹉C), ▽2.0 ﹉C(0 ~ 50 ﹉C) |
| BURN-OUT
detection |
| Thermocouple : OFF, UP / DOWN selection |
| RTD : OFF, UP selection (when Thermocouple or RTD BURN-OUT, the detection current : approx. 50 nA) |
|
| Measuring
Accuracy |
▽0.5%(FULL SCALE) |
| Input Range |
| Refer to "input signal and measuring range" |
| For thermocouple and RTD, the change is valid within the range of the input signal and measuring range table |
| For d.c voltage, the min/max voltage is possible within the each measuring range |
| and scaling is possible within the measuring condition |
|
| Power of
operating
sensors |
20 V d.c(internal resistance 1.2 k目) Max. 50 mA, 15 V d.c (internal resistance 790 目) |