     * HY-48I
    - Clear digital indication
  - Alarm (warning) set up
  - Simple temperature set up
  - Proportioning control or ON/OFF control

 
       
     
 

Model HY-48 I
Rated Voltage 110 / 220 V a.c, 60 Hz (universal) But, HY-48D, 48I are Selected by the Internal Dip S/W (Default : 220 V a.c)
Permissible Voltage
Fluctuation Range
Rated Voltage ▽10%
Consumption Power Approx. Max. 3 VA
Input Thermocouple, Resistive, DC Current, DC Voltage
Adjusting Sensitivity ▽ 0.2 % F.S (fixed)
Control Method
HY-8000, 72D, 48D HY-8200S
- Time Proportion ON/OFF - Time Proportion + ON / OFF
- ON / OFF + ON / OFF
Setting Method Set by BDC Switch
Display Method LED 7 Segment all Display
Control Output
Relay Output : Capacity 250 V a.c 3 A
(Resistive Load) Contact : 1c
SSR Output : 12 V a.c (Constant Voltage Pulse)
(Resistive Load: above 800目 )
Current Output : 4 - 20 mA d.c
(Resistive Load : Below 600目 )
Setting Accuracy Below ▽ 0.5 % F.S
Display Accuracy Below ▽1.0 % of Max. Range
Proportional Band
HY-8000S, HY-8200S, HY-72D : HY-48D
Approx.1 ~ 10 % of Max. Range (Variable) Approx. 3% of Max. Range (fixed)
Proportional Cycle Relay Output : 25 ~ 30 sec, SSR Output : 2 ~ 4 sec
External Input Resistance Thermocouple : Below 100 , Resistive : Below 10 目(But, the 3 Wires Should have the Same Resistance)
Resolution 1 ﹉C (pt100 目 - 49.9 ~ 199.9 : 0.1 ﹉C)
Dielectric Strength 2000 V a.c 50 ~ 60 Hz for 1 Minute (Between Terminals After Charging 2 Polar)
Operating Ambient
Temperature / Humidity
0 ~ 50 ﹉C, 35 ~ 85 % RH(Without Condensation)

Model Suffix Code Description
HY - HY-8000S, HY-8200S, HY-800S, HY72D, HY72I, HY-48D, HY-48I
Adjusting Action F 2 Position Control (ON / OFF)
P Proportional Action
Input K K (CA)
J J (IC)
R R (PR 13%)
D Pt 100 目 (KS standards)
P Pt 100 目 (DIN standards)
V 1 - 5 V d.c
C 4 - 20 mA d.c
Control Output M Relay Contact
C Current (4 - 20 mA d.c)
S SSR driving (Voltage Pulse 12 V d.c)
Alarm Output or Operation N None
O *High Limit Operation Output
Control Action R Reverse Action Control (for Heating Control)
D Direct Action Control (for Cooling Control)
Range Code Standard Range Code Number Selection
*Only For HY-8200S, it is standard.
*Mark the range code for temperature display (HY-800S, HY-72I, HY-48I) when composing the model name and suffix code
*Alarm Output can not be specified other than model name HY-8200S

Model /
Code No.
HY-8000S / 8200S HY-800S HY-72D / 72I HY-48D / 48I
Input Temp. Range Input Temp. Range Input Temp. Range Input Temp. Range
1     Pt -49 ~ 199     Pt -49 ~ 49
2 pt -99 ~ 99 Pt, K 0 ~ 399 *Pt -99 ~ 99 *Pt -99 ~ 99
3 pt -99 ~ 99 K 0 ~ 1199 Pt -99 ~ 199 Pt 0 ~ 199
4 pt 0 ~ 99 R 600 ~ 1699 Pt 0 ~ 99 Pt, K 0 ~ 299
5             *Pt, K 0 ~ 399
6 pt, K 0 ~ 199     Pt, K 0 ~ 199    
7 pt, K 0 ~ 299     Pt, K 0 ~ 299    
8 pt, K 0 ~ 399     *Pt, K 0 ~ 399    
9         K 0 ~ 599    
10 K 0 ~ 599     K 0 ~ 799    
11 K 0 ~ 799            
12         *K 0 ~ 1199    
13 K 0 ~ 1199     *R 599 ~ 1699    
14 K 600 ~ 1699            
* Display code is only available for model 72I, 48I